Blog › Measured energy

Reading an energy chart: three problems you can spot at a glance

You don’t need to be an engineer to read your system’s charts. Three recurring shapes, recognisable at a glance, point to most of the problems that push consumption up. Here is what they are and what to do.

May 27, 20266-minute readLeggi in italiano

Many systems now log their data, and many owners have access to a Grafana energy dashboard or something similar. Few look at it after the first week. The reason is simple: a chart full of lines says nothing if you don’t know what to look for.

The good news is that you don’t need to read everything. Most of the problems that make a heating system use more than it should can be recognised from three recurring shapes. In this article we describe them one by one, with the most likely causes and what to do. They are meant for people who manage a building, not those who designed it.

Three small charts side by side: flat consumption at night, a dense stepped line of on-off cycles, and a temperature that levels off below the red set point line
Three typical problems on an energy chart: consumption that doesn’t drop at night, too many starts, a zone that never reaches temperature. Example data.

Before you start: what to look at

To recognise the three problems you need three charts, which almost every monitoring system offers:

  • hourly consumption of the heat source, gas or electricity, over the last 24 hours or the last week;
  • heat source status, on or off, over the same period;
  • the temperature of each zone with its set point, the temperature it should be at.

Look at them on a normal day, not during a party or with the windows open for cleaning. And keep the outdoor temperature alongside: high consumption on a night at zero degrees is not a problem.

Problem 1: consumption doesn’t drop at night

What you see. On the hourly consumption chart, the night hours are as high as the day hours, or nearly. There is no “valley” you would expect while everyone sleeps and the system runs at set-back.

What it means. Night set-back is missing or not working. The system keeps daytime temperatures through the night.

The most common causes.

  • The zone schedules have no set-back, or have all been put on Comfort “to be safe”.
  • One zone was left in manual mode after a change.
  • The heat source is getting a demand from something else, for example hot water recirculation running all night.

What to do. Check the schedules zone by zone, and find out which demands reach the heat source at night. With underfloor heating the set-back should be moderate, two or three degrees, but it should be there.

Problem 2: too many starts

What you see. On the heat source status chart the line keeps going up and down: dozens of starts a day, each lasting a few minutes. The chart looks like a comb.

What it means. The heat source is short-cycling. Every start has a cost: it uses more energy at start-up, runs less efficiently and wears out sooner.

The most common causes.

  • The heat source is too powerful for the building and reaches temperature in minutes.
  • The gap between switch-on and switch-off temperatures, the hysteresis, is too small.
  • The flow temperature is higher than needed, so the heat source reaches it straight away.

What to do. Lower the heating curve, if there is one, as explained in the article on weather compensation. Widen the hysteresis and set a minimum run time. If the problem persists, the heat source is probably oversized: worth raising with the installer at the next service.

Problem 3: a zone never reaches temperature

What you see. On one zone’s chart the temperature rises but levels off below the set point and stays there for hours. The other zones reach temperature.

What it means. That zone is calling for heat and not getting it, or not enough. Meanwhile the heat source works for it, often at a higher temperature than needed.

The most common causes.

  • The zone’s actuator is faulty or stuck.
  • The zone’s loop is closed at the manifold, or has air in it.
  • The sensor is badly placed, for example near a window or on a cold wall, and reads lower than the real temperature.
  • The room needs more heat than expected: an exposed wall, an old window.

What to do. Start with the simplest check: touch the manifold and feel whether that zone’s loop warms up when the zone is calling. Then check where the sensor is. If everything is in order, the problem is in the room, and the data helps decide what work is needed.

A fourth shape worth knowing: creeping consumption

One last problem does not show in a day but over a month: consumption per degree day rising slowly, week after week. It means the system is getting less efficient: a dirty filter, a valve that no longer closes properly, a setting changed and forgotten. You only see it by comparing periods, as we described in the article on the six readings in a plant room.

What isn’t a problem

Learning to spot problems also means learning not to see them where there are none. Some shapes look odd but are normal.

  • A morning peak. After night set-back the system works harder to bring rooms back up to temperature. A short peak is normal; a peak lasting until noon means the set-back is too deep.
  • A zone above its set point in the afternoon. If the room faces west, the sun heats it for free. The system is off, and rightly so.
  • Different consumption on days with the same outdoor temperature. Wind, cloud, people at home, the oven on: a building doesn’t live by degrees alone.

Before taking action, always ask whether there is a simple explanation.

How often to look

Once everything is set up, a few minutes a week in the heating season are enough. A good rhythm is:

  • once a week, the three charts for a typical day;
  • once a month, consumption per degree day compared with the previous month and with the same month a year earlier;
  • straight away, when an alert arrives.

From alerts to charts

The three problems can also become automatic alerts: a zone calling for heat for more than three hours, too many starts in a day, night-time consumption above a threshold. In the Node-RED zone flow we showed how to build the first one, and in the Grafana plant room dashboard how to display the others.

Alerts do not replace a human eye, but they make sure the chart gets opened when it matters. That is where a system that uses too much becomes a system that uses the right amount.

Have your charts checked

If you have a Brick system, or any system that already logs consumption, send us an extract of the data: we will tell you what we see.